Parameter Teknis untuk 6kV, 10kV& 30kVA-2500kVA Dengan Trafo Tipe Kering Off Circuit
| (KVA) Kapasitas terukur | Kombinasi Tegangan | Simbol Grup Koneksi | Kerugian Tanpa Beban (W) | Kehilangan Beban (W) | Arus Tanpa Beban (%) | Impedansi Hubungan Pendek(%) | ||||
| Tegangan Tinggi (KV) | Penyadapan rentang Tegangan Tinggi | Tegangan Rendah (KV) | 130 derajat (B) (100 derajat ) | 155 derajat (F) (120 derajat ) | 180 derajat (H) (145 derajat ) | |||||
| 30 | 6 6.3 6.6 10 10.5 11 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 190 | 670 | 710 | 760 | 2 | 4 |
| 50 | 270 | 940 | 1000 | 1070 | 2 | |||||
| 80 | 370 | 1290 | 1380 | 1480 | 1.5 | |||||
| 100 | 400 | 1480 | 1570 | 1690 | 1.5 | |||||
| 125 | 470 | 1740 | 1850 | 1980 | 1.3 | |||||
| 160 | 540 | 2000 | 2130 | 2280 | 1.3 | |||||
| 200 | ±2X2.5% ±5% | 620 | 2370 | 2530 | 2710 | 1.1 | ||||
| 250 | 720 | 2590 | 2760 | 2960 | 1.1 | |||||
| 315 | 880 | 3270 | 3470 | 3730 | 1 | |||||
| 400 | 980 | 3750 | 3990 | 4280 | 1 | |||||
| 500 | 1150 | 4590 | 4880 | 5230 | 1 | |||||
| 630 | 1340 | 5530 | 5880 | 6290 | 0.85 | |||||
| 630 | 1300 | 5610 | 5960 | 6400 | 0.85 | 6 | ||||
| 800 | 1520 | 6550 | 6960 | 7460 | 0.85 | |||||
| 1000 | 1770 | 7650 | 8130 | 8760 | 0.85 | |||||
| 1250 | 2090 | 9100 | 9690 | 10300 | 0.85 | |||||
| 1600 | 2450 | 11000 | 11700 | 12500 | 0.85 | |||||
| 2000 | 3050 | 13600 | 14400 | 15500 | 0.7 | |||||
| 2500 | 3600 | 16100 | 17100 | 18400 | 0.7 | |||||
| 1600 | 2450 | 1220 | 12900 | 13900 | 0.85 | 8 | ||||
| 2000 | 3050 | 15000 | 15900 | 17100 | 0.7 | |||||
| 2500 | 3600 | 17700 | 18800 | 20200 | 0.7 | |||||
Parameter Teknis untuk 20kV & 50kVA-2500kVA Dengan Trafo Tipe Kering Off Circuit
| (KVA) Kapasitas terukur | Kombinasi Tegangan | Simbol Grup Koneksi | Kerugian Tanpa Beban (W) | Kehilangan Beban (W) | Arus Tanpa Beban (%) | Impedansi Hubungan Pendek(%) | ||||
| Tegangan Tinggi (KV) | Penyadapan rentang Tegangan Tinggi | Tegangan Rendah (KV) | 130 derajat (B) (100 derajat ) | 155 derajat (F) (120 derajat ) | 180 derajat (H) (145 derajat ) | |||||
| 50 | 20 22 24 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 340 | 1160 | 1230 | 1310 | 2 | 5.0 |
| 100 | 540 | 1870 | 1990 | 2130 | 1.8 | |||||
| 160 | 670 | 2350 | 2470 | 3460 | 1.8 | |||||
| 200 | ±2X2.5% ±5% | 730 | 2770 | 2940 | 3140 | 1.8 | ||||
| 250 | 840 | 3220 | 3420 | 3660 | 1.8 | |||||
| 315 | 970 | 3850 | 4080 | 4360 | 1.8 | |||||
| 400 | 1150 | 4650 | 4840 | 5180 | 1.1 | |||||
| 500 | 1350 | 5460 | 5790 | 6190 | 1.1 | |||||
| 630 | 1530 | 6450 | 6840 | 7320 | 1 | |||||
| 800 | 1750 | 7790 | 8260 | 8840 | 1 | |||||
| 1000 | 2070 | 9220 | 9780 | 10400 | 0.85 | |||||
| 1250 | 2380 | 10800 | 11500 | 12300 | 0.85 | |||||
| 1600 | 2790 | 13000 | 13800 | 14800 | 0.85 | |||||
| 2000 | 3240 | 15400 | 16300 | 17500 | 0.7 | 8.0 | ||||
| 2500 | 3870 | 18200 | 19300 | 20700 | 0.7 | |||||
| 2000 | 3240 | 16800 | 17800 | 19100 | 0.7 | |||||
| 2500 | 3870 | 20000 | 21200 | 22700 | 0.7 | |||||
Parameter Teknis untuk 35kV & 50kVA-2500kVA Dengan Trafo Tipe Kering Off Circuit
| (KVA) Kapasitas terukur | Kombinasi Tegangan | Simbol Grup Koneksi | Kerugian Tanpa Beban (W) | Kehilangan Beban (W) | Arus Tanpa Beban (%) | Impedansi Hubungan Pendek(%) | ||||
| Tegangan Tinggi (KV) | Penyadapan rentang Tegangan Tinggi | Tegangan Rendah (KV) | 130 derajat (B) (100 derajat ) | 155 derajat (F) (120 derajat ) | 180 derajat (H) (145 derajat ) | |||||
| 50 | 35 36 37 38.5 | ±2.5% ±5% | 0.4 | Dyn11 Yyn0 | 450 | 1340 | 1420 | 1520 | 2.3 | 6 |
| 100 | 630 | 1970 | 2090 | 2230 | 2 | |||||
| 160 | 0.79 | 2650 | 2810 | 3000 | 1.5 | |||||
| 200 | ±2X2.5% ±5% | 0.88 | 3130 | 3320 | 3550 | 1.5 | ||||
| 250 | 0.99 | 3580 | 3800 | 4060 | 1.3 | |||||
| 315 | 1170 | 4250 | 4510 | 4820 | 1.3 | |||||
| 400 | 1370 | 5100 | 5410 | 5790 | 1.1 | |||||
| 500 | 1520 | 6270 | 6650 | 7110 | 1.1 | |||||
| 630 | 1860 | 7250 | 7690 | 8230 | 1 | |||||
| 800 | 2160 | 8600 | 9120 | 9760 | 1 | |||||
| 1000 | 2430 | 9860 | 10400 | 11100 | 0.75 | |||||
| 1250 | 2830 | 12000 | 12700 | 13600 | 0.75 | |||||
| 1600 | 3240 | 14600 | 15400 | 16500 | 0.75 | |||||
| 2000 | 3820 | 17200 | 18200 | 19500 | 0.75 | |||||
| 2500 | 4450 | 20600 | 21800 | 23300 | 0.75 | |||||